L D POWER Transformers Pvt. Ltd.
An ISO 9002 : 2000 Certified Company


Single Phase Transformer

Applicable Standards
  • IEC (International Electro technical Commission)
  • ANSI (American National Standard Institution)
  • BS (British Standards)
  • IS (Indian Standard)
Specification

make conventional type, 1 Phase, 50 Hz, Oil immersed,naturally cooled, Pole mounted / Platform mounted, double wound with Aluminium / Copper, Step up/Step down core type continuous duty transformers having no load voltage ratio from 5 KVA to 100 KVA upto 33 KV Class with ‘A’ Class Insulation and designed to withstand Short Circuit, & Impulse Test in accordance to ANSI / IEC / BS / IS. Completely self Protected type Transformers are also available for protection on both HV & LV Side. Details of Characteristics & dimensions of standard transformers with standard fittings manufactured in accordance with ANSI C 57 latest., readily available in stock and can be delivered within 1 weeks from the date of order confirmation. The temperature rise will be 60/65° C in Oil/Winding respectively over a maximum ambient temperature as per ANSI. The transformers will be manufactured as per ANSI C 57 latest, complete with fittings/accessories as stated below.
KVA Efficiency
(%)
Voltage
Regulation(%)
W
(mm)
D
(mm)
H
(mm)
Oil
(l)
Weight
(Kg)
5 97.60 2.05 400 520 770 12 69
10 98.00 1.79 450 570 800 17 97
15 98.23 1.56 480 600 850 23 120
25 98.25 1.58 530 620 1030 65 205
37.5 98.58 1.26 650 650 900 38 244
50 98.29 1.60 670 650 950 45 253
75 98.53 1.30 740 720 950 62 340
100 98.72 1.18 795 750 100 78 440
167 98.92 1.15 850 825 1065 116 675


Note

Three Phase Tranformer

Applicable Standards
  • IEC (International Electro technical Commission).
  • ANSI (American National Standard Institution).
  • BS (British Standards).
  • IS (Indian Standard).
Description
P R O D U C T S

© copyright 2005 - 2006
Business website from www.netgables.com